OSHA Exit Sign Requirements
Quick answer: OSHA 29 CFR 1910.37 requires EXIT signs with โฅ6-inch letters, ยพ-inch strokes, illuminated to 5 ft-c, posted at every exit and along the egress path. Below: the full 2026 rulebook on letter size, illumination, placement, color, and "NOT AN EXIT" labels โ plus how exit signs connect to your evacuation map. Final review by a qualified safety professional, fire marshal, or AHJ is required.
Related guides: free evacuation map generator, fire evacuation map requirements, where to post maps, what to include on an evacuation map.
OSHA Exit Sign Requirements โ 29 CFR 1910.37(b)
Every requirement employers must meet for exit sign compliance
Sign Required at Each Exit
Each exit must be clearly identified by a sign visible from every direction of approach.
Letter Size & Legibility
'EXIT' letters minimum 6 inches high, 3/4-inch stroke width, plainly legible.
Visibility Distance
Signs must be visible from the maximum viewing distance along the route of exit access.
Color & Contrast
Letters must be distinctly visible with contrasting colors to the background.
'NOT AN EXIT' Marking
Doors that could be mistaken for exits must be marked 'NOT AN EXIT' or identified by actual use.
Illumination
Minimum 5 foot-candles on sign face (external) or 0.06 footlamberts (self-luminous/electroluminescent).
Emergency Power
Exit signs must remain illuminated during power failure (90 min minimum backup per NFPA 101).
Types of Exit Signs
Choose the right exit sign type for your facility
Internally Illuminated
Most common in new constructionLED or fluorescent lighting within the sign body. Energy efficient with built-in battery backup. Minimum 0.06 footlamberts luminance.
Advantages
- Low energy cost
- Built-in battery backup
- Long LED lifespan (50,000+ hours)
- Uniform illumination
Externally Illuminated
Common in existing buildingsSign face lit by external light fixtures providing at least 5 foot-candles on the sign surface. Requires separate emergency power.
Advantages
- Low initial cost
- Easy to replace sign face
- Compatible with existing fixtures
Self-Luminous (Tritium)
No power requiredContains tritium gas tubes that glow without electricity. No wiring, no batteries, no maintenance. Lifespan of 10-20 years.
Advantages
- Zero electricity needed
- No maintenance
- Works in any condition
- NRC licensed
Photoluminescent
Charging light requiredAbsorbs ambient light and glows in the dark. Must be charged by reliable light source. Meets UL 924 when properly installed.
Advantages
- No electricity needed
- Eco-friendly
- Low cost
- Code-compliant in many jurisdictions
"NOT AN EXIT" Sign Requirements
Under 29 CFR 1910.37(b)(5), any door, passage, or stairway that is neither an exit nor a way of exit access โ and is located in an area where it could be mistaken for an exit โ must be identified as such.
Doors That Need "NOT AN EXIT" Signs:
- Storage rooms along exit corridors
- Mechanical/electrical rooms near exits
- Basement stairways that don't lead outside
- Conference rooms opening onto exit corridors
- Restrooms near exit paths
- Elevator lobbies (elevators are not exits)
Pro Tip: Instead of "NOT AN EXIT," you can label the door with its actual purpose (e.g., "STORAGE," "MECHANICAL ROOM," "RESTROOM"). This is equally compliant and more informative.
Both "NOT AN EXIT" and functional labels are OSHA-aligned
Generate an Evacuation Map with Proper Exit Signage
Our AI marks every exit, exit sign, and "NOT AN EXIT" door on your evacuation map.
Create Your Exit Sign Compliance Evacuation Map
Drag & drop your floor plan here
or
PNG, JPG, HEIC, TIFF, BMP, PDF - Hand-drawn sketches work too!
Move, resize, and recolor every exit sign, route, and icon.
Create a free account to save and download in HD. No credit card required.FREE
Frequently Asked Questions
Is this evacuation map generator really free?
Yes โ you can generate your first OSHA-aligned evacuation map draft completely free. Just upload a floor plan and our AI drafts a professional map in about 30 seconds. No credit card required.
Are the generated maps aligned with OSHA?
Our AI drafts maps that follow OSHA 29 CFR 1910.36โ37 and NFPA 101 Life Safety Code standards. Every map includes clearly marked exits, fire extinguisher locations, assembly points, and directional evacuation arrows. Supervisor review is required before posting to your facility.
What file formats can I upload?
We accept JPG, PNG, and PDF floor plans. For best results, use a clear, high-resolution image of your floor plan with visible walls, doors, and rooms.
How long does map generation take?
Most maps are generated in 20โ40 seconds. Complex multi-floor plans may take slightly longer. You can download your map immediately after generation.
Can I edit the map after generation?
The generated map is a high-resolution image you can download and print. For custom edits or enterprise features like multi-floor support and branded maps, check our pricing plans.
Is my floor plan data secure?
Yes. All uploads are encrypted in transit (TLS 1.3) and processed in secure cloud environments. We do not share your floor plans with third parties.
Most Common Exit Sign Violations
OSHA inspectors cite these exit sign violations most frequently
Missing Exit Signs
Exits without any sign โ the most basic and most cited violation. Every designated exit must have a sign visible from every direction of approach.
Non-Illuminated Signs
Exit signs with burned-out bulbs, dead batteries, or insufficient illumination. Signs must maintain 5 foot-candles or 0.06 footlamberts at all times.
Missing "NOT AN EXIT" Signs
Doors that look like exits but lead to storage, basements, or dead ends. Employees can waste critical evacuation time trying these doors.
Obstructed or Hidden Signs
Exit signs blocked by equipment, inventory, decorations, or hanging displays. Signs must be visible at all times from every approach direction.
Undersized Lettering
Letters less than 6 inches high or strokes less than 3/4 inch wide. Small lettering isn't readable at distance, especially in smoke conditions.
No Emergency Backup
Signs without battery backup or generator connection. During power failures (when signs matter most), they go dark.
OSHA Exit Sign FAQs
Common questions about exit sign requirements and compliance
What are OSHA's exit sign requirements?
OSHA requires exit signs at every designated exit per 29 CFR 1910.37(b). Signs must be distinctly visible, illuminated to a minimum of 5 foot-candles, and use the word 'EXIT' in plainly legible letters not less than 6 inches high with 3/4-inch wide strokes. Self-luminous and electroluminescent signs must have a minimum luminance of 0.06 footlamberts. Signs must be placed so no point in the exit access is more than 100 feet from the nearest visible exit sign.
What color must OSHA exit signs be?
OSHA does not mandate a specific color for exit signs. However, NFPA 101 Life Safety Code specifies that exit signs must have contrasting colors with the letters clearly distinguished from the background. Most US facilities use red or green EXIT signs. Green is internationally preferred (ISO 7010) and is required in many countries. The key requirement is visibility and contrast, not a specific color โ but red and green are the industry standards.
Do exit signs need to be illuminated?
Yes. OSHA 29 CFR 1910.37(b)(6) requires that each exit sign must be adequately illuminated by a reliable light source providing at least 5 foot-candles on the sign face. Internally illuminated signs (self-luminous or electroluminescent) must provide at least 0.06 footlamberts. Exit signs must also remain illuminated during power failures using emergency backup power (battery or generator) for at least 90 minutes per NFPA 101.
How far apart must exit signs be placed?
Exit signs must be placed so that no point in the exit access corridor is more than 100 feet from the nearest visible exit sign (NFPA 101 Section 7.10.1.5). Additionally, exit signs are required at each designated exit doorway, at points where the exit access direction is not immediately apparent, and near each change of direction along the exit access path. Intermediate directional signs are needed in longer corridors.
When are 'NOT AN EXIT' signs required?
OSHA 29 CFR 1910.37(b)(5) requires that any door, passage, or stairway that is not an exit or does not lead to an exit โ but could be mistaken for one โ must be marked 'NOT AN EXIT' or identified by a sign indicating its actual use (e.g., 'STORAGE ROOM,' 'BASEMENT'). This prevents confusion during evacuations and ensures occupants don't waste time trying doors that don't lead to safety.
What are the letter size requirements for exit signs?
OSHA 29 CFR 1910.37(b)(2) requires: the word 'EXIT' in plainly legible letters not less than 6 inches high, with the principal strokes not less than 3/4 inch wide. If a directional arrow is used, it must be placed to show the direction of travel. If additional text appears (such as floor number), the EXIT lettering must remain predominant. The sign must be visible from all directions of approach.
Are exit signs required in all buildings?
Exit signs are required in virtually all commercial, industrial, and institutional buildings. OSHA 29 CFR 1910.37(b)(1) requires exit signs at each exit. Exceptions are limited: single-exit rooms where the exit is immediately visible to all occupants may not require a sign. However, best practice (and many local codes) recommend signs even in single-exit rooms. Residential buildings follow different codes (IRC) but multi-family dwellings require them.
What backup power is required for exit signs?
Exit signs must remain illuminated during power failures. NFPA 101 Section 7.9 requires emergency lighting (including exit sign illumination) to operate for at least 90 minutes on backup power. Options include: battery backup units built into the sign, central battery systems, or emergency generators. Battery-backed signs must be tested monthly (30-second test) and annually (90-minute full discharge test) per NFPA 101 Section 7.9.3.
Mark Every Exit on Your Map
Our AI identifies exits, marks signs, and creates OSHA-aligned evacuation maps โ free and instant.
Free โ No credit card required โ OSHA & NFPA compliant
Important Legal Disclaimer
The Occupational Safety and Health Administration (OSHA) does not approve, endorse, recommend, or certify any commercial products or software. This platform is a compliance assistance tool only and is not affiliated with or endorsed by OSHA or any government agency.
All AI-generated evacuation maps, safety plans, and compliance documents must be reviewed, verified, and approved by a qualified safety professional, fire marshal, licensed engineer, or appropriate authority before being posted, distributed, or used for emergency planning purposes.
Employers retain full legal responsibility for workplace safety under the Occupational Safety and Health Act of 1970 (OSH Act). Users are solely responsible for ensuring compliance with all applicable local, state, and federal regulations. This software does not guarantee OSHA compliance.
This software does not constitute legal, safety consulting, engineering, or professional advice. Content is for informational purposes only. Users should consult qualified safety professionals and legal counsel for compliance guidance specific to their operations.
While we strive for accuracy, workplace safety regulations change frequently. We make no warranties regarding the accuracy, completeness, or current validity of any information. Users must independently verify all regulatory requirements applicable to their specific circumstances.
To the maximum extent permitted by law, OSHAMap, its owners, operators, affiliates, and licensors shall not be liable for any direct, indirect, incidental, special, consequential, or punitive damages arising from use of this service, including but not limited to workplace injuries, OSHA violations, regulatory fines, property damage, or any other losses.
Cost comparisons and savings estimates are based on industry averages for professional safety consultant fees and are provided for informational purposes only. Actual costs, savings, and results may vary significantly based on your specific situation.
By using OSHAMap, you acknowledge that you have read, understood, and agree to be bound by these terms. For complete terms, see our Terms of Service and Privacy Policy.