🏥NFPA 101 Ch.20/21 · NFPA 99 · CMS §482.41 · ADA

Healthcare Clinic Evacuation Plan Maps

Built for clinics, ambulatory surgery centers, urgent care, infusion centers, and outpatient buildings. Our AI produces a posted-ready evacuation plan that respects ADA accessible routes, marks areas of refuge, shows horizontal exits to the next smoke compartment, supports defend-in-place strategy for non-moveable patients, and notes medical-gas zone valves and bulk-O₂ storage. Free to start — supervisor sign-off required before posting.

RACERescue · Alarm · Confine · Evacuate
ADARefuge & accessible routes
NFPA 99Medical-gas zone valves
Two-versionLobby + back-of-house export

No credit card. Joint Commission EM documentation-friendly.

3 Simple Steps:
1Upload Floor Plan
2Select State & Industry
3Get Your Map

Seven Healthcare Considerations Your Map Must Address

Each one is a real CMS, NFPA, or Joint Commission expectation.

ADA Accessible Routes

ADA 2010 §206 + IBC §1104. Every primary egress route must be accessible. Mark wheelchair-accessible doors (32" clear), ramps under 1:12 slope, and avoid stairs as the only path.

  • Power-operated doors
  • Door pull-side clear space
  • Threshold < 0.5"
  • Tactile exit signage
🛡️

Areas of Refuge

ADA + IBC §1009. Smoke-protected location with two-way communication for assisted evacuation. Mark every refuge with the international symbol of accessibility and the device location.

  • Pressurized stair landing
  • Two-way intercom
  • Refuge capacity sign
  • Smoke-rated doors
🚪

Horizontal Exits & Smoke Compartments

NFPA 101 §18/19/20: clinics partition into smoke compartments by 1-hr fire-rated walls with smoke doors. Horizontal exit lets staff move patients laterally without going down stairs.

  • Smoke-door cross-corridor
  • 1-hr fire-rated separation
  • Magnetic hold-opens with alarm release
  • Refuge area capacity calc
🛏️

Defend in Place

For OR, infusion, ICU, NICU patients who cannot be moved. NFPA 101 explicitly endorses this for healthcare. Posted map must show the protected compartment and the staging room within it.

  • Smoke-compartment staging
  • Charge nurse role assignment
  • Oxygen-zone shut-off plan
  • Re-evacuation trigger criteria
💨

Medical-Gas Zones & Bulk O₂

NFPA 99: every smoke compartment has its own zone shut-off valve. Bulk O₂ storage requires 50 ft fire-rated separation. Map should show every valve location and the manifold room.

  • Zone-valve labels (Vac, O₂, Med Air, N₂O)
  • Manifold room location
  • Bulk O₂ tank pad
  • O₂-enriched treatment rooms
🧫

Infection Control During Evac

Isolation rooms (negative or positive pressure) need a route that does not push pathogens through clean corridors. Mark isolation suites and an alternate assembly point for evacuated isolation patients.

  • Airborne-infection isolation rooms
  • Protective-environment rooms
  • Alternate isolation assembly
  • PPE-don area on the route
👥

Staff Role Assignments

CMS §482.41(b)(2) requires named roles. The posted map should print a small legend keyed to laminated wallet cards: charge nurse, floor warden, patient mover, records runner, accountability officer.

  • Numbered role badges
  • Wallet-card alignment
  • Shift-roster annotations
  • Drill-after-action capture

Generate Your Clinic Evacuation Plan Map

Upload your floor plan — ADA refuge, AED, eyewash, and Class A/C extinguishers placed automatically.

✓ ADA accessible routing✓ Area-of-refuge symbols✓ Defend-in-place compartments✓ AED + first-aid placement✓ Lobby + back-of-house export

Healthcare Clinic Regulations Cheat Sheet

CMS, NFPA, OSHA, ADA, and the Joint Commission — one line each.

Federal & CMS

  • §
    OSHA 1910.38 — Written EAP including patient evacuation procedures.
  • §
    OSHA 1910.1030 — Bloodborne pathogens (sharps, spill response).
  • §
    OSHA 1910.1200 — HazCom (lab reagents, cleaning chemicals).
  • §
    CMS §482.41 — Hospital physical environment + life safety.
  • §
    CMS §416.41 — ASC environment of care, EAP.
  • §
    CMS §485.623 — Critical access hospital life safety.
  • §
    ADA 2010 §206, §216, §703 — Accessible routes, signage, refuge.

NFPA + Joint Commission

  • 📕
    NFPA 101 Ch.20 / 21 — New / Existing Ambulatory Health Care.
  • 📕
    NFPA 101 Ch.18 / 19 — New / Existing Health Care Occupancies (hospitals).
  • 💉
    NFPA 99 — Health Care Facilities Code (medical-gas, electrical).
  • 🧯
    NFPA 10 — Portable extinguishers — Class A & C in clinics, K near kitchens.
  • 🚨
    NFPA 72 — Fire alarm and signaling (audible + visible in patient rooms).
  • 🏥
    Joint Commission EM.02.01.01 — Documented evacuation plan + HVA.
  • 🏗️
    IBC §1009 — Accessible means of egress (refuge areas).

What Our Generator Places Automatically for Clinics

ADA Accessible Routes

Routes default to power-operated, level-threshold paths. Stairs are marked but not the primary egress.

❤️

AED + First Aid

AED at lobby and break room; first-aid kits at nurses' stations.

👁️

Eyewash at Lab & Decon

Auto-placed at lab, decon, and chemical rooms (premium); 55 ft service expectation noted.

🧯

Class A + C Extinguishers

Class A throughout, Class C near MRI/imaging electrical, Class K near kitchen.

🚪

Smoke Compartment Doors

Editor lets you mark cross-corridor smoke doors and label horizontal exits.

🅿️

Outdoor Assembly

Snapped outside the building footprint, with isolation-patient alternate assembly note.

🚨

Pull Stations + Strobes

Placed at every exit; strobes flagged for hearing-impaired patient areas.

🛡️

Area-of-Refuge Markers

Place via editor at stair landings; map prints the international symbol of accessibility.

Five Inspector Findings Specific to Clinics

Medical-gas zone valve unmarked on the map

NFPA 99 finding. Add valve labels per smoke compartment.

Defend-in-place not explained on the posted map

Inspectors expect to see "Evacuate horizontally to next smoke compartment" as the primary action.

Area-of-refuge missing two-way comm device

ADA + IBC §1009.8 finding. Mark the device location and test annually.

Elevator used as primary egress

Code requires "Do NOT use elevator" signage. Map should label stairs as primary.

Isolation room route crosses public corridor

Add an alternate route + alternate assembly area for evacuated isolation patients.

If This Sounds Like Your Clinic…

20-Room Family Practice

Single floor, lobby + 18 exam rooms + 1 procedure room + lab. Lobby map plus back-of-house map with O₂ tank storage and lab eyewash.

Multi-Specialty ASC

3 ORs, 6 PACU bays, infusion suite, GI lab. Defend-in-place strategy for OR + PACU; horizontal exit to north wing; lobby map ADA-symbol heavy.

4-Story Outpatient Tower

One map per floor. Refuge areas at each stair landing. Elevator override note. Lobby + back-of-house versions per floor. Joint Commission HVA-ready.

Talk to a Healthcare Compliance Specialist

For ASC accreditation surveys, multi-site clinic networks, or Joint Commission EM audits — book a session with our healthcare team.

Healthcare Clinic Evacuation Plan — FAQ

How is a healthcare clinic evacuation plan different from an office plan?

Clinics, ambulatory surgery centers (ASCs), urgent care, and outpatient buildings combine the visiting public (mobility, language, cognitive variation) with patients who may be sedated, ambulatory-with-assistance, non-ambulatory, on IV poles, in wheelchairs, or in active treatment. The evacuation map has to show ADA accessible routes, areas of refuge, horizontal exits to the next smoke compartment, defend-in-place zones (because OR or infusion patients may not be moveable), and the staff role assignments (charge nurse, runner, accounting headcount). A generic office map covers none of this.

What standards apply to a healthcare clinic evacuation map?

Federal: 29 CFR 1910.38 (EAP) + 1910.1030 (bloodborne pathogens) + 1910.1200 (HazCom). Fire & life safety: NFPA 101 Life Safety Code Chapter 20 (New Ambulatory Health Care) or Chapter 21 (Existing) for outpatient facilities; Chapter 18/19 for hospital units; NFPA 99 Health Care Facilities Code for medical-gas zones and emergency power. CMS Conditions of Participation (42 CFR 482.41 for hospitals, 416.41 for ASCs) require a written plan and posted maps. The Joint Commission EM (Emergency Management) standards expect a hazard vulnerability analysis (HVA) and a documented evacuation plan. ADA 2010 Standards govern accessible routes, signage, and areas of refuge.

What is an area of refuge and does my clinic need one?

An area of refuge (ADA + IBC §1009) is a smoke-protected location where a person who cannot use stairs can wait for assisted evacuation. Required in most buildings over 1 story without a fire-rated elevator or sprinkler system. Even sprinklered clinics often designate refuge areas at stair landings or in horizontally separated smoke compartments. Your map must show every refuge area with the international symbol of accessibility, the two-way communication device, and the route to it from each treatment room.

What is "defend in place" and when does it override evacuation?

NFPA 101 §18/19 + CMS §482.41 explicitly allow healthcare occupancies to defend in place rather than evacuate, because moving a sedated, ventilated, or post-op patient can be more dangerous than the fire. The map should show smoke compartments (separated by 1-hour rated walls with smoke doors), horizontal exits to the next compartment, and the defend-in-place staging room. Full building evacuation is a last resort. Posted maps should label primary action as "Defend in place, evacuate horizontally to next smoke compartment" rather than "Exit the building".

How do I handle ambulatory vs non-ambulatory patient movement?

NFPA 101 Annex A.18.2.4.4 describes the RACE protocol (Rescue, Alarm, Confine, Evacuate) and the order: ambulatory patients walk-out, semi-ambulatory escorted, wheelchair-bound rolled, bedridden moved via evac chair or sled. Your map should show staging points for evac chairs and Med-Sleds, the bariatric route (wider doorway path), and the elevator override for fire-service operation. Marking these on the posted map gives the floor crew a visual aid during the chaos.

What about medical gas, oxygen-enriched atmospheres, and O₂ tank storage?

NFPA 99 governs medical-gas systems. The map must show the medical-gas zone shut-off valves (each smoke compartment has its own), the bulk-O₂ storage location with its 50 ft fire-rated separation, the manifold room, and any oxygen-enriched treatment area (PFTs, neonatal). During evacuation the charge nurse closes the zone valve for the affected compartment. Mark valve locations clearly — these are the #1 missed item on inspector walk-throughs.

How does the map handle infection control during evacuation?

Isolation rooms (negative pressure for airborne; positive pressure for protective) become contamination considerations during evacuation. The map should mark each isolation suite, show a route that avoids passing other patients through a known infectious corridor, and identify the alternate assembly point for evacuated isolation patients. This was an explicit COVID-era CMS guidance and remains best practice.

What about staff role assignments — does the map show them?

Yes. CMS §482.41(b)(2) requires named roles. Best practice is to print a staff-role legend on the map: Charge Nurse (incident command), Floor Wardens (sweep each room), Patient Movers (with evac equipment), Records/Charts Runner (grabs the chart cart), Accountability Officer (headcount at assembly point), Stairway Monitor (controls flow). Print laminated wallet cards keyed to the same numbering on the map.

Do I need separate maps for the front lobby vs back of house?

Yes. The front lobby map is the public-facing posted map — large, clear, ADA-symbol heavy, English/Spanish typical. Back-of-house maps include staff-only details: med-gas valves, O₂ storage, controlled-substance room (no obvious markings on the public map), generator location, fire pump room. Generate two versions from the same floor plan.

How does our generator handle multi-story clinics with elevators?

Upload each floor. The generator outputs one map per floor with stair markings, elevator override notes ("Do NOT use elevator — fire service operation"), and per-floor area-of-refuge markers. The assembly point on each map points to the same outdoor location with a re-converge note. For multi-story buildings with horizontal exits between wings, the map shows smoke-compartment boundaries.

Healthcare Clinic Evacuation Map: The Full Implementation Playbook

Outpatient clinic, ambulatory surgery center, dental practice, urgent care, multi-specialty group. The map ties together CMS, NFPA 101 Chapter 20, ADA, and your state department of health licensing.

01

Classify your occupancy correctly

Are you Ambulatory Health Care (NFPA 101 Ch 20/21) or Business Occupancy (Ch 38/39)? An ASC providing anesthesia is Ambulatory Health Care; a primary care clinic is usually Business. The classification drives sprinkler, alarm, and egress requirements.

02

Defend-in-place vs full evacuation

For clinics with non-ambulatory patients (post-procedural recovery, sedated), the immediate response may be horizontal relocation to the next smoke compartment, not full building evacuation. Map shows smoke-barrier doors and refuge areas.

03

ADA accessible routes are the primary route

If your clinic serves patients with mobility limitations (most do), the wheelchair-accessible egress IS the primary egress. Stairs are secondary. Map highlights the level-threshold route in safety green.

04

Bariatric considerations

If you have a bariatric program, plan for transport of patients up to 700 lb. Map identifies the bariatric egress door (must be 48”+ clear width) and the refuge area with a structural floor rating for the load.

05

Identify oxygen and medical gas storage

NFPA 99 + 55 govern medical gas storage. Map shows bulk O2, N2O, MedAir storage rooms. Oxygen rooms get a ”NO IGNITION” annotation. Locked gas cylinders also marked.

06

Plan for radiation and MRI rooms

MRI cannot tolerate ferrous equipment near the bore. Map calls out the 5-Gauss line. Fire response cannot bring oxygen tanks, SCBA tanks, or rescue carts into Zone IV. Pre-stage non-ferrous evac aids.

07

Quarterly fire drills (required by Joint Commission)

EM.02.02.05 — drills under varied conditions. Track timing per drill, document on map revision.

08

Isolation-precaution patient transport

For airborne-isolation patients (TB, measles, COVID), the map identifies an alternate alternate assembly area or transport vehicle staging. Don’t expose the public.

Standards Deep-Dive: Healthcare Clinic

NFPA 101 Ch 19/20
Existing / New Ambulatory Health Care. Anesthesia-providing facilities. Smoke compartmentation, defend-in-place strategy, alarm requirements.
NFPA 101 Ch 38/39
Existing / New Business Occupancies. Most primary care, urgent care, dental — fewer special requirements but full means-of-egress still applies.
NFPA 99
Health Care Facilities Code. Medical gas, electrical, environmental systems. Risk category I/II/III/IV based on patient-injury potential.
NFPA 55
Compressed Gases and Cryogenic Fluids Code. Bulk medical gas storage rules.
CMS 482.41 / 485.623
CMS Conditions of Participation — Physical Environment. Hospitals + critical access. Adopted 2012 LSC. Tag K-741 (utility), K-345 (drills) etc. apply to map currency.
42 CFR 416.44
CMS ASC Conditions for Coverage. Physical environment for Medicare-certified ASCs. EAP + map review required.
CMS Emergency Preparedness Rule
42 CFR 482.15 / 485.625 / 416.54. All-hazards EAP, communication plan, training, testing.
Joint Commission EM.02.02.05
Emergency Management Standards. Annual exercise, varied scenarios, after-action review.
ADA Title III §4.1.3(9)
Accessible means of egress. Same number of accessible exits as required exits.
29 CFR 1910.1030
Bloodborne pathogens. Sharps containers, exposure-control plan — map annotates sharps station, eyewash.
29 CFR 1910.36 – 38
Means of egress + EAP. Federal baseline applies to clinical workers.

Smoke Compartments & Defend-in-Place Strategy

NFPA 101 Ch 19/20 requires smoke compartments not exceeding 22,500 sq ft, with smoke-barrier doors. The strategy is to move at-risk patients laterally into the adjacent compartment rather than down a stair. Maps annotate smoke-barrier doors with a thick magenta dashed line and a ”Smoke Barrier” label.

Each compartment must have sufficient refuge area for the occupants of the adjacent compartment — typically 30 net sq ft per ambulatory patient, 50 per non-ambulatory. Maps show the refuge capacity per compartment.

MRI Suite Special Considerations (NFPA 99 + ACR Guidelines)

  • Zone I = unrestricted (lobby).
  • Zone II = supervised (changing rooms).
  • Zone III = restricted (control room).
  • Zone IV = magnet room. Map shows the 5-Gauss line clearly.
  • Ferromagnetic SCBA, oxygen tanks, ladders MUST NOT enter Zone IV during fire response — pre-stage non-ferrous (aluminum) firefighting equipment if your AHJ permits.
  • Quench button location annotated. Quench releases liquid helium → evacuate via the quench-route exit.

Patient Transport During Evacuation

Three categories: ambulatory (walks out under own power), partial-assist (uses cane/walker, may need stair-chair), non-ambulatory (gurney/wheelchair, requires staff). Map identifies muster locations by category — non-ambulatory patients may go to a separate refuge area within the building rather than the parking-lot assembly.

Stair-evac chairs (Evac+Chair, Stryker) at every stairway top. Maps annotate locations and quantity. Staff trained per OSHA 1910.38(e).

Healthcare Clinic ROI Snapshot

$$$ (loss of Medicare)

CMS deficiency can pull certification. Most clinics rely on Medicare/Medicaid revenue. Map non-currency is a Tag K-finding.

$15,625

OSHA serious citation. Worker-safety side overlaps with patient-safety side.

RFI

Joint Commission Requirement for Improvement. Costs survey time + corrective action plan. Each RFI on the EM standards stacks.

$2,500-7,500

Per-clinic consultant fee for new evacuation maps + EAP review. Replace with our generator at zero marginal cost per facility.

100%

Of Joint-Commission accredited facilities that fail their tracer for evacuation drills get an RFI. Maps drive drills.

200ms / occupant

Estimated decision-time savings during evac with a clear color-coded route map vs an outdated unmarked drawing.

Glossary: Healthcare Terms

ASC
Ambulatory Surgery Center. Medicare-certified outpatient surgical facility.
CMS
Centers for Medicare & Medicaid Services. Federal regulator that drives most clinical compliance.
LSC
Life Safety Code. NFPA 101. CMS-adopted 2012 edition (with revisions).
EAP / EOP
Emergency Action Plan / Emergency Operations Plan. Required by OSHA + CMS respectively.
Smoke Compartment
Area bounded by smoke barriers, used as refuge. NFPA 101 Ch 19/20.
Defend-in-Place
Sheltering at-risk patients in adjacent smoke compartment rather than full evacuation.
Horizontal Exit
Smoke barrier between two compartments same floor; counts as an exit.
Area of Refuge
ADA-required wheelchair-accessible space for awaiting assisted egress.
Tag K
CMS surveyor finding categories for Life Safety. K-741 = utility systems; K-345 = drills.
EOC
Joint Commission Environment of Care standards. EC.02.03.01 through EC.02.06.01.
EM
Joint Commission Emergency Management standards. EM.01–EM.04.
RFI
Requirement for Improvement. Joint Commission finding.

FAQ Extension: Multi-Specialty Clinics & Multi-Tenant Buildings

If your clinic shares a building with non-medical tenants (most professional medical offices do), the building owner provides the building EAP — but you provide the tenant-suite EAP. Map your suite, including the door to the public corridor, the path to the building stair, and the exterior assembly point. Coordinate the assembly point with the building manager.

If you operate satellite locations (a primary practice + 3 retail-pad urgent cares), each location is a separate EAP and map. Maintain version control centrally.

Clinic Inspector Casebook

Findings drawn from Joint Commission surveys, CMS validation surveys, state DOH inspections, and OSHA visits to healthcare facilities. Use as a pre-survey audit.

FINDING 01

Smoke door propped open

NFPA 101 §19/20. Doors must self-close.

FINDING 02

Crash cart blocking egress corridor

1910.37(a)(3). Move to designated alcove; map annotates location.

FINDING 03

Oxygen storage near electrical panel

NFPA 99 §11.6. Map marks oxygen room; separate ignition sources.

FINDING 04

Wheelchair-accessible exit locked at 5pm

1910.37(d)(1) + ADA. Cannot lock egress from inside.

FINDING 05

Stair-evac chair missing top of stair

ADA + Life Safety. Add chair + train staff.

FINDING 06

Bariatric route doesn’t accommodate 700 lb

Re-design or add bariatric door (48” clear).

FINDING 07

Refuge area exceeds compartment occupant load

30 sq ft ambulatory + 50 sq ft non-ambulatory. Re-size.

FINDING 08

Sharps container at chest height blocks corridor view

1910.1030. Mount at 48” with line-of-sight clear.

FINDING 09

MRI quench-route exit unlabeled

NFPA 99 + ACR guideline.

FINDING 10

AED battery dead

Monthly check; AED on map but dead is worse than absent.

FINDING 11

Eyewash valve corroded

ANSI Z358.1 weekly activation.

FINDING 12

Drill log missing month

Joint Commission EM.02.02.05.

FINDING 13

Assembly point on fire-lane

NFPA 1 + IFC §503.

FINDING 14

Isolation patient assembly co-mingled with general public

Add alternate.

FINDING 15

Sedated patient PACU evacuation undocumented

Per ASA guidelines + facility EAP.

FINDING 16

Pediatric reunification plan absent

EM.02.02.07. Map annotates parent-pickup zone.

FINDING 17

Generator transfer-switch room locked

NFPA 110.

FINDING 18

Battery backup < 90 min

NFPA 101 §7.9.2.6.

FINDING 19

Map revision predates suite remodel

Re-generate post-remodel.

FINDING 20

Floor-warden vests missing

EAP role unstaffed.

Clinic Drill Script (40 minutes)

  1. T-0:00 Brief charge nurse, floor wardens.
  2. T-0:05 Trigger alarm in exam suite.
  3. T-0:06 Charge nurse declares: defend-in-place vs full evac.
  4. T-0:08 Sweep rooms (knock + announce).
  5. T-0:12 Move non-ambulatory to refuge.
  6. T-0:15 Headcount at assembly.
  7. T-0:20 Re-entry briefing.
  8. T-0:30 After-action with patient-safety officer.
  9. T-0:40 Update map / EAP, log in Joint Commission tracer file.

Patient Transport Training Modules

  1. Patient classification — ambulatory / partial-assist / non-ambulatory / sedated.
  2. Stair-evac chair operation.
  3. Bed transport through smoke barrier doors.
  4. Oxygen during transport — quantity, valve, tip protection.
  5. Isolation patient — PPE for staff, dedicated route.
  6. Pediatric reunification — wristbands, codes, parent area.
  7. Bariatric transport — slide boards, designated team.
  8. Defend-in-place criteria — when not to move.

CMS Tag K Reference Card

TagSubjectMap relevance
K-100General requirementsEAP referenced
K-211Means of egress maintainedDirect
K-291Emergency lightingMap annotates path
K-293Exit signsDirect
K-321Hazardous areasMap shows separation
K-345DrillsMap = drill prop
K-353Sprinkler systemsMap shows coverage
K-355StandpipesDirect
K-363DoorsSmoke barriers
K-372Building constructionCompartmentation
K-741Utility systemsGenerators, transfer switch
K-911EAP and drillsMap is anchor

Joint Commission EM Standards Mapping

EM.01.01.01 (hazard vulnerability analysis), EM.02.01.01 (EOP development), EM.02.02.03 (communication), EM.02.02.05 (drills + exercises), EM.02.02.07 (children + patients with special needs). The evacuation map satisfies the visual deliverable for several of these.

State Licensing Overlays

California Title 22, Texas TAC 25, New York 10 NYCRR Part 405, Florida 59A — all add facility-specific egress, drill, and posting requirements on top of NFPA 101. Use your state DOH licensing standards as the upper bound and the federal/NFPA stack as the floor.

30 Common Clinic Questions

  1. Ambulatory vs Business occupancy? Anesthesia & recovery = Ambulatory.
  2. Smoke compartment size? 22,500 sq ft max NFPA 101.
  3. Sprinkler required? Most facilities yes.
  4. Generator required? >Risk Category 2 NFPA 99.
  5. Drill frequency? Quarterly varied conditions.
  6. Drill record retention? 3 years minimum.
  7. Map size? 11×17 minimum.
  8. Wheelchair-accessible route? Primary route.
  9. Stair-evac chair? At each stair.
  10. Bariatric door width? 48” clear minimum.
  11. MRI Zone IV evac aid material? Non-ferrous.
  12. Quench-route door? Marked + unlocked.
  13. Eyewash check? Weekly.
  14. AED check? Monthly.
  15. Crash-cart location on map? Yes.
  16. Sharps box height? 48”.
  17. Refuge area sizing? 30 ambulatory / 50 non-ambulatory.
  18. Pediatric reunification spot? Map annotates.
  19. Visitor accountability? Sign-in log.
  20. Vendors/service techs? Same as visitors.
  21. Cleaning crew at night? Brief on map + alarm.
  22. Telehealth-only staff? Not subject.
  23. Off-site lab couriers? Brief at intake.
  24. Multi-suite tenants? Per-suite EAP + map.
  25. Building owner EAP? Coordinate, don’t duplicate.
  26. Active-shooter overlay? Run/hide/fight add-on.
  27. Severe weather? Interior corridor.
  28. Earthquake? Drop/cover/hold; evac after if structure suspect.
  29. Power outage? Generator + battery-backed lighting.
  30. Customer privacy in map? Don’t show patient names; show room labels generically.