🖥️NFPA 75 · 76 · 855 · OSHA 1910.38

Data Center Evacuation Map Generator

Mission-critical evacuation planning for hyperscale halls, colo cages, edge POPs, and enterprise server rooms. Our AI reads your floor plan and produces a posted-ready map that respects hot/cold-aisle containment, lithium-ion battery rooms, clean-agent discharge zones, generator yards, and single-staffed night-shift realities — all in the 90 seconds it takes to brew a coffee.

NFPA 75/76IT & telecom fire
NFPA 855Battery rooms
30 secClean-agent evac window
Tier III/IVConcurrent-maintenance ready

No credit card. SOC 2 / PCI-friendly outline rendering.

3 Simple Steps:
1Upload Floor Plan
2Select State & Industry
3Get Your Map

The Five Data-Center-Only Hazards Your Map Must Address

Lifted from real facility audits and reflected in NFPA 75, 76, and 855.

🌡️

Hot-Aisle Containment Egress

Containment panels at row ends become egress doors during an alarm. NFPA 75 §8.5 requires they not impede travel. Posted map should label every row-end as a Push-to-Exit transit point.

  • Sliding vs hinged row-end doors
  • Containment ceiling drop-down panels
  • Aisle pressure differential indicators
  • Emergency lighting under panels
🔋

Lithium-Ion UPS Battery Rooms

NFPA 855 governs stationary storage > 20 kWh. Thermal runaway emits flammable + toxic gases. Assembly point must be upwind of the exhaust louver, not just outside the door.

  • Gas-detection alarm tie-ins
  • Class D / lithium-rated extinguishers
  • 2-hour fire-rated separation
  • Cell-level temperature monitoring
☁️

Clean-Agent Discharge Zones

FM-200, Novec 1230, IG-541 discharge in 10 seconds with 30-second pre-discharge alarm. Map must show protected outline, pre-discharge horn, manual abort station, and the evac route out before discharge.

  • NFPA 2001 zone boundaries
  • Abort / manual pull stations
  • Discharge nozzle pattern
  • Cylinder room with restricted access

Generator Yard & Fuel

Diesel day tanks, paralleling switchgear, ATS. Egress should route along the opposite face of the building from the yard during any generator-bus event.

  • NFPA 30 day-tank bunding
  • NFPA 70E arc-flash boundary at ATS
  • Fuel-transfer line clearance
  • Yard-only assembly never
🌙

Single-Staff Night Shift

NFPA 76 §4 + OSHA 1910.38(e): operator must be able to evacuate, alarm, and re-enter unaccompanied. Map needs explicit "lock behind you" note and a re-badge-free assembly point.

  • NOC as primary YOU ARE HERE
  • Two-exit redundancy
  • Re-entry badge fallback
  • Assembly visible from public road

Generate Your Data Center Evacuation Map Now

Hot/cold aisles, battery rooms, generator yards, clean-agent zones — placed automatically.

✓ Hot-aisle row-end exits✓ Battery-room upwind assembly✓ Clean-agent zone annotation✓ Generator-yard routing✓ Per-cage zone maps

Data Center Regulations Cheat Sheet

Federal OSHA, NFPA, and the consensus standards your auditor reads.

OSHA 29 CFR 1910

  • §
    1910.38 — Written EAP for the data center occupancy.
  • §
    1910.157 — Class C extinguishers within 75 ft, Class D for lithium battery rooms.
  • §
    1910.147 — LOTO for paralleling switchgear, ATS, and PDU work.
  • §
    1910.146 — Battery rooms can qualify as permit-required confined spaces during work.
  • §
    1910.95 — Hearing conservation in cooling-fan-dense halls (often > 85 dBA).
  • §
    1910.165 — Audible + visible alarms in noisy halls.
  • §
    1910.305 — Wiring methods (relevant to overhead busway and PDU work).

NFPA + Industry Standards

  • 🏢
    NFPA 75 — Fire Protection of Information Technology Equipment.
  • 📡
    NFPA 76 — Fire Protection of Telecommunications Facilities.
  • 🔋
    NFPA 855 — Stationary Energy Storage Systems (lithium UPS battery rooms).
  • ☁️
    NFPA 2001 — Clean Agent Fire Extinguishing Systems.
  • NFPA 70E — Electrical Safety in the Workplace (arc-flash at switchgear).
  • 🌬️
    ASHRAE TC 9.9 — Hot/cold-aisle thermal guidelines.
  • 🏆
    Uptime Institute Tier III/IV — Concurrent maintainability informs exit redundancy.

What Our Generator Places Automatically for Data Centers

🌡️

Row-End Exit Markers

Every containment row end annotated as a Push-to-Exit transit point.

🔋

Battery-Room Upwind Assembly

Assembly point snapped away from battery exhaust louvers when an NFPA 855 room is tagged.

☁️

Clean-Agent Zone Outline (Premium)

Hatched outline + 30-second pre-discharge note + manual abort marker.

🔒

LOTO at Electrical Rooms

Premium-tier dashed LOTO badges at electrical, mechanical, server, and machine_area rooms (cap 8).

🧯

Class C + Class D Clusters

Class C near IT equipment, Class D at lithium battery rooms.

📍

NOC as YOU ARE HERE

Single anchor with one route per exit; primary route bolded in ISO 7010 safety-green.

🅿️

Re-Badge-Free Assembly

Snapped outside the building footprint, upwind of generator yard and battery exhaust.

🛡️

SOC 2 / PCI Friendly

Cage outlines without revealing tenant content. Outline-only export option available.

Five Most Common Data Center Inspector Findings

Containment doors not labeled as egress

NFPA 75 §8.5 violation. Mark every row end as Push-to-Exit on the posted map.

Battery room with no upwind assembly

NFPA 855 + OSHA 1910.38(c)(3). Snap assembly upwind of exhaust louvers.

Generator yard egress crossing fuel-transfer line

NFPA 30 finding. Route along the opposite face of the building.

Clean-agent zones missing pre-discharge signage on the map

NFPA 2001 §1.5. Add hatched outline + 30-second note.

Single-egress server hall exceeds 75 ft travel

NFPA 75 §6 / NFPA 101 chapter 38. Add a second exit or reduce travel distance.

If This Sounds Like Your Facility…

Hyperscale 25 MW Build

Two halls, MMR, UPS gallery with 1.2 MWh lithium, generator yard with 4 paralleled units. Generate one master map per hall + battery-room map with upwind assembly.

Colocation with 200 Tenant Cages

One master map + one zone map per cage posted at the cage door. Tenant techs see the closest exit from where they are working. Outline-only rendering keeps cage contents private.

Edge POP at a Cell Site

Single room, single operator. NFPA 76 + single-staff night-shift mode. NOC console as the YAH, two exits, re-badge-free assembly visible from the public road.

Talk to a Data Center Compliance Specialist

For hyperscale, multi-site colo rollouts, or NFPA 855 battery-room buildouts — book a session with our team.

Data Center Evacuation Map — FAQ

Why does a Tier III/IV data center need a specialized evacuation map?

A data center floor is not an office. Hot-aisle / cold-aisle containment panels create egress mazes; lithium-ion UPS battery rooms can experience thermal runaway with no warning; clean-agent (FM-200, Novec 1230, IG-541) suppression discharge requires immediate evacuation; generator yards mix fuel storage with high-amperage transfer switches; and most facilities run single-staffed on night shift. A generic office map misses every one of these. Our generator places hot-aisle annotations, battery-room assembly notes, clean-agent discharge alerts, and routes that exit away from the generator yard.

What standards apply to data center evacuation maps?

OSHA 29 CFR 1910.38 (EAP), 1910.157 (extinguishers), 1910.147 (LOTO for power systems), 1910.146 (battery rooms can be permit-required confined spaces), 1910.95 (hearing — server hall noise often exceeds 85 dBA). NFPA 75 (Fire Protection of Information Technology Equipment), NFPA 76 (Fire Protection of Telecommunications Facilities), and NFPA 855 (Stationary Energy Storage Systems — governs battery rooms). The Uptime Institute Tier Standard does not regulate egress, but Tier III/IV concurrent-maintenance requirements often create redundant exits that should be reflected on the map.

How do hot-aisle containment doors interact with egress routes?

NFPA 75 §8.5 requires that containment systems not impede egress. Sliding or hinged containment doors at row ends must be marked on the evacuation map as exit-through points with a "Push to Exit" indicator. Many citations come from doors labeled as cold-aisle access only, which inspectors read as blocked egress. Our map marks every containment row end as a transit point and the row-end door as an exit-through component.

What about clean-agent suppression — FM-200, Novec 1230, IG-541?

Clean-agent systems discharge in 10 seconds and create an immediate evacuation condition. NFPA 2001 requires a pre-discharge alarm with at least 30 seconds notice. Your posted map must show: (1) the protected zone outline, (2) the pre-discharge alarm horn location, (3) the discharge nozzle pattern, (4) the manual abort/pull station, and (5) the route that exits the zone before discharge completes. The premium tier of our generator marks clean-agent zones with a hatched outline and a 30-second-evac note.

How do you handle UPS and lithium-ion battery rooms?

NFPA 855 governs stationary energy storage systems above 20 kWh. Lithium-ion thermal runaway produces flammable + toxic gases that can outpace normal egress. Battery rooms need: (1) their own assembly point upwind of the room exhaust louvers, (2) a Class D / lithium-rated extinguisher at the entry, (3) an audible + visible alarm tied to gas detection, and (4) routes that do NOT cross the room exhaust plume. Our map snaps an assembly note away from the exhaust path when the battery room is tagged.

What about generator yards and fuel storage?

Diesel day tanks (NFPA 30) + paralleling switchgear (NFPA 70E arc-flash boundary) + automatic transfer switches. The egress route should never cross between the generator and its fuel transfer line during a generator-bus event. Mark the generator yard as a hazard outline and route evacuation along the opposite side of the building.

How does a single-staffed night shift change the map?

NFPA 76 + OSHA 1910.38(e): you must designate enough trained employees to assist in evacuation regardless of shift size. With a single operator on night shift, the map should mark: (1) the operator console as the primary YOU ARE HERE, (2) the closest two exits, (3) an explicit "lock the door behind you" note for unattended entries, and (4) the assembly point reachable without re-badging. Our single-anchor YAH model fits this perfectly.

Do colo facilities need different maps from enterprise data centers?

Yes. Colocation facilities have visiting tenant techs unfamiliar with the facility. Posted maps should be at every cage/suite entrance, not just the main entrance. Tenant-specific zones should still show the full facility outline so the tech in cage 14B can see the exit at cage 1A and the one at the loading dock. Generate one master map + one zone map per cage and post both.

How does our map handle restricted-access compliance (SOC 2, PCI-DSS, FedRAMP)?

Like ITAR — life safety beats access control. The map can show room outlines without revealing tenant data. The assembly point cannot be inside an access-controlled cage. We snap it to an unrestricted outdoor area near the main entrance with the upwind correction applied.

How fast can I generate a data center evacuation map?

About 90 seconds on free tier (Gemini Flash) and 2–3 minutes on premium (Gemini Pro + HD upscale). Upload the floor plan, our Vision model identifies server rows, battery room, UPS room, generator yard, and likely exits. The deterministic overlay places EXIT pills, evacuation arrows from a single YAH, extinguishers, AED, pull stations, clean-agent annotations (premium), LOTO badges, and the upwind assembly point. Then export to PDF/PNG/SVG.

Data Center Evacuation Map: The Full Implementation Playbook

From a 5,000 sq ft enterprise edge POP to a 50 MW hyperscale, the egress story is dominated by clean-agent suppression, restricted access, and the fact that the people on-site at 3am may be a single contracted operator. Plan for that scenario.

01

Map by white-space hall, not by building

A multi-hall facility has independent fire areas. Each hall gets its own evacuation map. Common-area maps in the front-of-house cover lobby, customer suites, NOC.

02

Identify clean-agent discharge zones

NFPA 2001 covers FM-200, Novec 1230, Inergen, FK-5-1-12. NFPA 12 covers CO2 (now prohibited for normally-occupied spaces). Each discharge zone gets a hashed overlay and a ”EVACUATE ON ALARM” annotation. Pre-discharge time is typically 30-60 seconds.

03

Map hot/cold aisle layout so egress paths are obvious

In containment configurations, the egress aisle may not be the cold aisle. End-of-row doors and emergency-exit-only end caps need labels.

04

Address battery rooms (UPS) per NFPA 855

Lead-acid, VRLA, or Li-ion — each has separate egress and ventilation rules. Li-ion BESS (battery energy storage systems) under NFPA 855 require explosion-vent area sizing and fire-rated separation. Map the BESS room as its own fire compartment.

05

Show generator yards and fuel-storage envelopes

NFPA 110 emergency standby generators are normally outside. Map the yard, the fuel tanks (above- or below-ground), and the 25 ft (typical) electrical-clearance envelope around switchgear.

06

Coordinate with the customer suite cages

Customers in colocation cages may have their own access procedures. Map labels each cage; the master EAP describes the cage-by-cage notification chain.

07

Plan for the single night-shift operator

One operator, one badge. Map must be navigable by someone who started the shift two hours ago. YOU ARE HERE pins at every door, two exits visible from every hall, no riddles.

08

Mantrap and re-entry strategy after evac

Mantraps fail in a fire. Map calls out the emergency-egress-only doors that bypass mantraps. After evac, re-entry requires manual badging and an accompanied escort — note this on the map and in the EAP.

Standards Deep-Dive: Data Center

NFPA 75
Standard for the Fire Protection of Information Technology Equipment. Sprinkler vs gaseous suppression decisions, room construction, smoke detection, raised-floor concerns.
NFPA 76
Standard for the Fire Protection of Telecommunications Facilities. Central offices, wire centers, transmission facilities. Cable management and life-safety requirements.
NFPA 855
Standard for the Installation of Stationary Energy Storage Systems. Governs BESS / UPS battery rooms. Li-ion-specific explosion control.
NFPA 2001
Clean Agent Fire Extinguishing Systems. Discharge concentrations (NOAEL), egress time, room integrity test (door fan test).
NFPA 110
Standard for Emergency and Standby Power. Generator yard, transfer switches, fuel storage. Egress must respect 36” working clearance.
NFPA 70 (NEC) 645
Information Technology Equipment. Article 645 lets you use special wiring methods IF the room meets specific egress, smoke-detection, and emergency-power-disconnect rules. Map shows EPO buttons.
NFPA 101 §40.2
Industrial Occupancies — Special Purpose. Most data centers fall under industrial use; some lease space is business occupancy. Mixed-occupancy maps note the boundary.
29 CFR 1910.36 – 38
Means of egress + EAP. Federal baseline.
29 CFR 1910.157
Portable fire extinguishers. Class A + C (electrical) for IT rooms.
TIA-942-B
Telecommunications Infrastructure Standard for Data Centers. Rating I/II/III/IV. Concurrent maintainability for III; fault tolerance for IV. Map mirrors the redundancy.
Uptime Institute Tier
Tier Classification System. Tier III + IV facilities must have independent egress paths matching the dual-power-path topology.

Clean-Agent Discharge Egress Planning

Pre-discharge alarm sequence: smoke detector (cross-zone) → pre-action / pre-discharge audible → typically 30-60 seconds → discharge. Personnel must be out before discharge. NFPA 2001 sets a 5-min egress design for normally-occupied spaces, but practical data center design targets <60 seconds. Map shows the nearest emergency exit from any point in the hall within ≤75 ft travel distance.

After discharge: agent concentration may exceed NOAEL (FM-200 = 9% NOAEL; design is 7%) but should remain below LOAEL. Do not re-enter without ventilation. Map shows the agent abort station — operator can pause discharge if they confirm false alarm before count-down completes.

Battery / BESS Room Specifics (NFPA 855)

  • Li-ion BESS: Max 600 kWh per room without enhanced controls. Explosion-vent area per NFPA 68 sized by stoichiometry.
  • VRLA / lead-acid: Hydrogen ventilation per IEEE 484. Map ventilation grilles and exhaust fans.
  • Eyewash: Required for any flooded lead-acid bank. 10-second reach.
  • Spill containment: Curbing/bunding around flooded cells. Map notes containment area.
  • Egress: Two doors per room over 1,000 sq ft. Both door-knob hardware (not magnetic-hold).
  • Suppression: Water mist (NFPA 750) increasingly common for Li-ion; clean agent ineffective on thermal runaway.

The Single-Operator Night Shift Scenario

3:17am. A smoke detector trips in Hall B. The operator is sitting in the NOC eating noodles. He has 30 seconds before pre-action discharge to confirm or abort. The map on his wall is more important than anything else in the building.

Design implication: (a) the operator’s YOU ARE HERE is at the NOC, (b) the egress route is the shortest path to the parking-lot assembly area without passing through Hall B, (c) the re-entry path for the responding fire department is annotated — they will come through the loading-dock door, not the lobby, because the lobby is on the wrong side of Hall B.

Mantrap, Vestibule, and Re-Entry After Evac

Card-access mantraps are common at data-center perimeters. In a fire alarm, NFPA 101 §7.2.1.6 requires mechanical fail-safe — doors must unlock or auto-open. Map labels each mantrap ”EMERGENCY EXIT ENABLED” and notes the re-entry procedure (typically manual override by responding fire department or facility security with escort).

Multi-Building Hyperscale Campus Mapping

A 50 MW campus may have 4 data halls, 1 admin building, 1 generator pad, 1 chiller plant, 1 substation. Six separate maps minimum. Plus a campus master map at the gate showing all six and the access road, hydrant grid, and fire-marshal staging area.

Data Center ROI Snapshot

$5,600 / minute

Average data center outage cost (Uptime Institute 2024). A delayed discharge or wrong-direction evac compounds this.

$2.5M

Average Li-ion BESS thermal-runaway insurance loss. NFPA 855 compliance is the cheapest insurance discount available.

3-7 days

Customer-suite restoration time after a hall evacuation. SLA penalties for IaaS providers stack.

$15-25k

Per-hall consultant cost for inspector-grade evacuation maps. Replace at zero marginal cost.

100%

Tier III/IV operators we surveyed required current maps for SOC 2 + ISO 27001 audits.

12 mo

Map refresh cadence required by most carrier and customer audit programs.

Glossary: Data Center Terms

BESS
Battery Energy Storage System. Governed by NFPA 855.
Clean Agent
Gaseous fire suppression that doesn’t leave residue. FM-200, Novec 1230, Inergen, FK-5-1-12. NFPA 2001.
EPO
Emergency Power Off. NEC Article 645 requirement for IT rooms. Big red button.
Mantrap
Two-door interlocked vestibule for access control. Must fail-safe in alarm.
Hot/Cold Aisle
Containment configuration alternating intake (cold) and exhaust (hot) aisles between racks.
White Space
The raised-floor data hall where IT equipment lives.
Gray Space
Support infrastructure space — UPS, switchgear, mechanical.
NOC
Network Operations Center. The 24/7 staffed monitoring room.
SOC 2
Service Organization Control 2. Audit program; physical security + availability controls reference the EAP.
Tier III/IV
Uptime Institute classification. III = concurrent maintainability, IV = fault tolerance.
NOAEL
No Observed Adverse Effect Level. Concentration of clean agent that’s safe for short occupancy.

FAQ Extension: Colocation and Customer Cages

Colocation customers in cages need to receive the evacuation map at lease execution and at any subsequent revision. Their own employees count toward the hall occupant load — your EAP must include their estimated headcount. Annual joint drill recommended.

If you operate carrier-neutral telecom meet-me rooms, those are typically NFPA 76 telecom facilities. Maps follow NFPA 76 cable-management and life-safety guidance, which is similar to but distinct from NFPA 75.

Data Center Inspector Casebook

Findings from facility audits, SOC 2 reviews, fire-marshal walkthroughs, and customer site visits. Use as a pre-audit.

FINDING 01

Hall door blocked by cabling cart

1910.37(a)(3). Map’s ”egress aisle” annotation creates clear-zone expectation.

FINDING 02

EPO button covered by tape

NEC Article 645. Map annotates EPO location; coverage = nuisance-prevention failure.

FINDING 03

Clean-agent abort station missing

NFPA 2001. Each discharge zone needs abort station inside the protected envelope.

FINDING 04

Mantrap fail-secure on alarm

NFPA 101 §7.2.1.6. Mantraps must fail-safe. Reconfigure access control.

FINDING 05

Generator yard fence inside electrical clearance

NFPA 110 + NEC. Fence too close to switchgear.

FINDING 06

Li-ion BESS without explosion vent

NFPA 855. Vent area per NFPA 68.

FINDING 07

Single-operator without 2-way radio

OSHA 1910.38(c)(2). Map shows assembly point; comms gap mitigated by radio policy.

FINDING 08

Hot-aisle containment door fails to open in alarm

Hot-aisle doors must release on alarm if they would impede egress.

FINDING 09

Customer cage with no posted map

Customers need same posting as your own staff.

FINDING 10

Floor-tile lifter blocked behind racks

Maintenance tool — needed for under-floor work. Map annotates location.

FINDING 11

Sprinkler heads painted over after rebuild

NFPA 13. Replace; map verifies coverage.

FINDING 12

Smoke-detector cross-zone misconfigured

Pre-action requires cross-zone; single-zone = full discharge on single alarm.

FINDING 13

Fuel-fill cap unsecured at generator yard

NFPA 30. Diesel spillage on apparatus pad.

FINDING 14

Cable tray weight load exceeded

Add hangers; map notes cable-tray location for inspection.

FINDING 15

Lobby vestibule door blocked open

Smoke control fails. Door must close.

FINDING 16

Loading dock egress route through hall

Re-route around hall, not through.

FINDING 17

Battery-room eyewash missing

Flooded lead-acid → required.

FINDING 18

Tier IV facility with single egress path

Mirror the fault-tolerance topology in egress.

FINDING 19

Map shows incorrect hall labels after re-numbering

Re-generate.

FINDING 20

Sub-contractor without map at sign-in

Add copy at security desk.

Data Center Drill Script (60 minutes including comms)

  1. T-0:00 Pre-brief operations + security + on-call NOC manager.
  2. T-0:05 Trigger smoke detector in Hall B (test mode).
  3. T-0:06 Pre-discharge alarm sounds; operator abort decision window.
  4. T-0:07 Operator activates abort (drill mode).
  5. T-0:08 Evac Hall B; operator + any vendor on-site.
  6. T-0:10 Headcount at parking assembly. Confirm customers in cages notified.
  7. T-0:15 Re-entry briefing with hypothetical fire-marshal.
  8. T-0:25 SOC 2 documentation update.
  9. T-0:45 After-action with Tier III/IV concurrent-maintainability impact analysis.
  10. T-1:00 Map / EAP update.

NOC Operator Decision Tree

  1. Alarm activated — confirm visually via camera if possible.
  2. If confirmed false → abort + reset.
  3. If confirmed real or unknown → allow discharge + evac.
  4. Notify on-call manager + customer success.
  5. Place ARFF / 911 call.
  6. Walk to assembly point with map + radio.
  7. Account for any vendor / customer on site.
  8. Do not re-enter until fire department clears.

SOC 2 + ISO 27001 Auditor Talking Points

Common Criteria CC6.4 (physical access), CC7.1 (system operations), CC7.3 (security incidents) all touch evacuation planning. Current map + drill records + EAP referenced in security policies = clean evidence packet. ISO 27001 A.7.5 (physical security perimeters) and A.7.11 (supporting utilities) similarly reference EAP.

Vendor Access & Smart-Hands Coordination

Smart-hands technicians on customer hardware come and go. Each must sign in with badge + watch a 60-second safety brief that includes the map. Post the map at the visitor desk + smart-hands intake; require acknowledgment on the badge issuance form.

Multi-Region Operator Considerations

If you operate 5+ facilities across regions, central security + EHS cannot maintain maps in CAD. SaaS-generated maps with central master + per-site posting solves the version-control problem. Per-site fire-marshal annotations vary by jurisdiction — Texas SFM, Virginia state code, NY FDNY all add overlays.

30 Common Data Center Questions

  1. How often update? Annually + on hall/MEP changes.
  2. Where post? At hall entry, NOC, loading dock, lobby.
  3. Smart-hands signing? Yes.
  4. Customer cage requires posted copy? Yes.
  5. Tier III vs IV impact on map? Show both egress paths.
  6. Clean agent timing? 30-60s pre-discharge.
  7. EPO behavior? Cuts IT power; protects egress lighting on UPS.
  8. Battery room separation? Fire-rated per NFPA 855.
  9. Li-ion BESS limit per room? 600 kWh without enhanced controls.
  10. Mantrap fail-safe? Required.
  11. Egress lighting hours? 90 min battery NFPA 101.
  12. Diesel storage limit? Per NFPA 30 + local AHJ.
  13. NOC manning policy? Risk-based; many ops single-staff overnight.
  14. Cage customer notification path? PA + cage-specific phone.
  15. Assembly point distance? Beyond fall zone + apparatus access.
  16. Fire-marshal annual review? Common in most jurisdictions.
  17. Smoke compartment in white-space? Often single compartment per hall.
  18. Compressed-gas in DC? Rare — annotate if present.
  19. Map size at hall door? 11×17 lit + glazed.
  20. SOC 2 audit cycle? Annual.
  21. ISO 27001 cycle? 3-year with annual surveillance.
  22. Customer SOC 2 sharing? Bridge letters with appendix.
  23. Cybersecurity incident interplay? Separate from physical EAP.
  24. Workplace violence overlay? Run/hide/fight add-on.
  25. Tornado/severe weather shelter? Interior corridor.
  26. Earthquake? Drop/cover/hold then evac if structure suspect.
  27. Pandemic? Reduce headcount; spread shifts.
  28. Power-utility loss? On generator; map shows EPO + transfer-switch room.
  29. Customer escort policy after evac? Re-entry by appointment.
  30. Map medium at NOC? Wall-mounted + tablet copy on iPad in dispatch dock.